Emergency Lighting for Schools: BS 5266-1 Duties, Testing and Exit Signage Explained

2 September 2026News8.4 min
Illuminated green fire exit sign and emergency luminaire in a school corridor

Schools must provide emergency lighting that allows safe evacuation when normal lighting fails, designed to BS 5266-1 and tested under the regime set out in BS EN 50172. In practice that means emergency luminaires along every escape route and in open teaching areas, illuminated exit signage, brief monthly function tests, an annual full-duration test and a log book recording all of it. This guide sets out who is responsible, where the luminaires go and how a summer refurbishment is the cheapest moment to close the gaps.

Who is legally responsible for emergency lighting in a school?

Fire safety law places duties on the responsible person: depending on structure, the headteacher, the trust's estates lead, the governing body or the local authority. The responsible person must ensure the premises have adequate emergency lighting, that it is maintained in working order, and that testing is carried out and recorded. The duty cannot be delegated away by hiring a contractor; the contractor does the work, the responsible person owns the outcome.

Two standards carry the technical weight. BS 5266-1 is the code of practice for emergency lighting design: where luminaires are needed, what light levels escape routes require and how long the system must run. BS EN 50172 specifies the testing and record-keeping regime. A fire risk assessment that finds inadequate emergency lighting creates an action the school must close, and inspectors, insurers and HSE guidance on workplace duties all point back to the same evidence: the design, the test records and the log book.

Where does a school need emergency luminaires?

BS 5266-1 works outward from the escape route. The standard positions cover:

  • Escape routes: corridors, stairs and final exits, lit to defined minimum levels along the centre line, with extra attention at changes of direction and level.
  • Exit doors and the signage above them, so the way out is identifiable in darkness and smoke.
  • Open areas above a threshold size, including halls, dining rooms, libraries and large open-plan teaching spaces, so occupants can reach an escape route from anywhere in the room.
  • High-risk task areas, such as science prep rooms and DT workshops, where a sudden blackout mid-task is itself dangerous.
  • Points of emphasis: firefighting equipment, fire alarm call points, first aid points and plant rooms.
  • Toilets above a minimum size and accessible toilets, which evacuation plans routinely forget.

Duration is normally three hours for premises like schools, which supports both evacuation and the decision to re-occupy or send pupils home in a prolonged outage.

What products do the job?

Emergency provision comes in two forms, and most schools use both. Emergency conversion packs turn a standard luminaire into an emergency one: the LOKI PRO+ 600×600 classroom panel offers an emergency pack option, so the panel lighting the room also covers the open-area requirement with no extra ceiling penetrations. Dedicated emergency luminaires then handle the specific tasks: the CLIO ultra slim exit sign marks final exits and direction changes, the SOTERIA 4-in-1 emergency exit unit covers multiple mounting and legend configurations from one product, and AMMA emergency spots provide discreet escape route and open-area coverage where a full panel is unnecessary. The complete range is in the emergency lighting category.

Exit signage deserves its own line in the schedule. Signs must use the standard running-man pictogram, be visible at the required viewing distance, and form a continuous chain: from any point in the building, the next sign should always be visible. A signage walk-through during design, following each escape route as an unfamiliar visitor would, catches the gaps a desk exercise misses.

What testing does BS EN 50172 require?

Monthly: a brief function test of every emergency luminaire and exit sign. Simulate a mains failure (usually via key switches on the lighting circuits), confirm every unit illuminates, restore power, record the result and any failures.

Annually: a full rated duration test, normally three hours. Every luminaire must still be lit at the end of the period. Batteries near end of life pass the monthly flick test and fail the annual one, which is exactly why both exist.

Always: record everything in the emergency lighting log book: test dates, results, failures and remedial actions. The log book is the first document a fire officer or insurer asks for, and an empty one is treated as evidence the testing never happened.

Plan the annual test for a holiday or weekend, because the batteries then need up to 24 hours to recharge, during which protection is reduced. The summer break is the natural slot, alongside any installation work.

Why is a refurbishment the right moment to fix emergency lighting?

Because the marginal cost collapses. The access equipment is on site, the ceilings are open, the electrician is already wiring every room and the school is empty. Adding emergency packs to panels being installed anyway, and scheduling CLIO or SOTERIA units along the escape routes, costs a fraction of a standalone emergency project a year later. It also produces one coherent system with one commissioning record, rather than layers of additions from different decades.

The design step matters as much as the hardware. The free lighting design service from Signature LED Lighting's in-house engineers schedules emergency provision room by room alongside the general lighting: which panels carry emergency packs, where the exit signs sit, and the duration and category for each space. The output gives the contractor a priceable schedule and gives the school the design documentation BS 5266-1 expects. Like every general luminaire, emergency products come with a 5-year warranty, two years of it on site, with terms set out on the onsite warranties page.

Frequently asked questions

Can teaching staff or the caretaker do the monthly tests?

Yes. The monthly function test is deliberately simple: operate the test facility, walk the route, confirm every unit lights, record the result. A caretaker or site manager with a basic briefing and a clear log book template handles it comfortably; many schools pair it with the weekly fire alarm test so it never gets forgotten. The annual full-duration test is more involved, because failures need investigating and battery replacements often follow, so most schools place it with their electrical contractor. What no school should do is skip recording: an untested system and an unrecorded test look identical to an inspector.

What is the difference between maintained and non-maintained emergency luminaires?

A non-maintained emergency luminaire stays off in normal conditions and lights only when the mains fails: the standard choice for classrooms and corridors that are well lit anyway. A maintained luminaire is permanently lit and continues on battery in a failure: required for exit signs and usual in spaces that go dark in use, such as halls during performances. Most school schemes mix the two: non-maintained packs in panels, maintained exit signage throughout, and maintained fittings in assembly and drama spaces. The design should state the mode for every emergency device, because the two behave identically in a test and differently in real life.

How long do emergency batteries last, and what do they cost to maintain?

Emergency battery packs typically need replacement every four to six years depending on type, temperature and how often they are discharged. The annual duration test is what reveals decline: units that drop out at two hours are telling you the battery is on its way. Budget for rolling replacement rather than crisis response, and keep the fitting schedule from the design pack so the right packs are ordered first time. Self-test luminaires reduce labour by running their own function and duration tests and indicating faults via a status LED, which is worth weighing on large sites where the monthly walk-round takes hours.

Do exit signs have to be illuminated, or are photoluminescent signs enough?

Escape route signage on schools' final exits and direction changes should be illuminated so it remains visible the moment lighting fails, which is why exit signs are specified as maintained devices. Photoluminescent signs depend on being charged by ambient light and fade with time, so they supplement rather than replace illuminated signage in a building like a school. Products such as the CLIO ultra slim exit sign and the SOTERIA 4-in-1 unit cover the standard legend, arrow and mounting combinations, and the 4-in-1 format helps contractors hold one product that adapts on site rather than stocking four variants.

Our school has emergency lighting but no records. Where do we start?

Start with a survey, not a guess. Walk the building, list every emergency luminaire and exit sign, then run a function test followed by a full duration test out of hours. The results sort the estate into working units, failed units and gaps where coverage is missing entirely. From there, open a log book dated from the survey, fix the failures, and schedule the gaps into the next refurbishment phase. If a lighting upgrade is planned anyway, fold the emergency works in: a free design pass produces the compliant layout, and the installation cost largely disappears into the main project.

Does emergency lighting work with DALI or other control systems?

Yes, with one non-negotiable rule: the emergency function must operate independently of the control system. A mains failure must light the emergency luminaires regardless of what the DALI bus, timers or sensors are doing. Within that rule, control integration adds genuine value: DALI emergency devices can run automated function and duration tests and log results centrally, replacing manual walk-rounds with an exception report. For schools installing DALI in halls and theatres anyway, specifying DALI emergency variants in those spaces is a small increment that pays back in reduced testing labour every month thereafter.

Close the gaps this summer

If your fire risk assessment has emergency lighting actions outstanding, or your log book has more blank pages than entries, the summer holiday is the time to fix it properly. Send your floor plans to the Signature LED in-house design team for a free emergency lighting layout alongside the general scheme, then contact the team to talk through products, testing and timescales. Life. Illuminated.